2 ZONE CONVENTIONAL EVOLUTION FIRE ALARM PANEL

In Stock

CHLORIDE UK Conventional Fire Alarm Panel, EVOLUTION SERIES have 2-16 zones.
CFP-7002/E, CFP-7004/E, CFP-7006/E, CFP-7008/E and CFP-7016/E are 2, 4, 6, 8 and 16 zones respectively.

Category:

Description

CHLORIDE UK Conventional Fire Alarm Panel, EVOLUTION SERIES have 2-16 zones.
CFP-7002/E, CFP-7004/E, CFP-7006/E, CFP-7008/E and CFP-7016/E are 2, 4, 6, 8 and 16 zones respectively.
They are designed by the leading technology and microprocessor based devices, they are user-friendly and simple to understand.
All the system conditions are displayed on the panel LCD and via separate indicator led as well.
The panel supervises system troubles conditions and displays them on the screen. With the Reset, Alarm, Cancel Alarm, Silence, Test and Evacuate buttons, user can simply operate the system functions. The general system indicators are Power, Ready, Pre-alarm, Fire Alarm, Cancel Alarm, Silence and Evacuate indicator led are displayed on the left side of panel. The Trouble indicator led are Ac Loss, Battery Error, Siren Error, Line Cut and Line Short circuit indicators are displayed in the right side on the panel.
There are also Alarm Relay Output, Trouble Relay Output and Siren Output onboard
The devices are manufactured in SMD Technology and complies with EN 54-2/4 standard.
The panels are compatible with all detectors and devices that comply with EN54 standards. The panel also have inbuilt auxiliary power supply outputs 24VDC, 400mA For installation of additional devices that needs external power like gas, Flame, Beam Detectors etc, It also has 2A,24vdc unfused output from the panel power supply unit, so there is no need of additional power source as they are available onboard
The installer can connect 20 numbers of Smoke or Heat detectors and unlimited Manual Call Points per every zone to the Evolution Series Fire centrals.
By the electronic filters on every zone, the device will not be affected by the high frequency interference.
There are hardware and software preventions from electromagnetic interference, noises on the mains power, short circuits and faulty connection on the cabling.

Product Features

• CFP-7002/E is a 2 Zones Evolution fire Panel
• Have Screen Display
• Each Zone Can Accommodate 20 Smoke/Heat Detectors And Unlimited MCP
• Zone Name Can Be Written And Display In The Screen
• Uses Regulated Power Supply Unit
• Real Time Clock
• 100 Event Log With Time And Date Stamp
• 2×16 Alphanumeric LCD Display
• Short-Circuit And Open Circuit Indication,
• Classic Plastic Front Case design.
• Back Box Metal Body,
• User-friendly Installation And Programming,
• Day/Night Mode Operation
• 2 Supervised Siren Output, 400mA
• Alarm And Error Relay Outputs,
• 24V Auxiliary Power Supply Output, 400Ma
• It also has 24vdc, 2A unfused output from the panel power supply unit
• 2x12V/7Ah Battery For Power Back Up
• Turkish – English Menu
• EN54-2/4 Compatible.
• Panel Dimensions: 29×33.5×10.5cm, Weight: 3100gr.

Technical Specifications

Specification Value
Operating Voltage 180–240Vac
Power 100W max
Battery Type Lead-Acid Sealed Battery
Battery Capacity 2 × 12V / 7Ah
Count of Zones 2, 4, 6, 8, 16
Active Detectors per Zone 20 pieces / Zone
Maximum Load per Zone 120R
Passive Detectors per Zone Unlimited
End of Line Resistor 4.7KΩ
Battery Short Circuit Protection Yes
Operating Temperature -10°C ~ +55°C
Humidity  % 95
Siren Outputs 1,2
Output Type Normally Open
Contact Rate 1 A @ 30Vdc
Fuse 400 mA Automatic Reset
End of Line Resistor 6.8KΩ (6.8K–20K)
Maximum Voltage 30V
Alarm Relay Output
Output Type Normally Open (NO) / Normally Closed (NC)
Contact Rate 1 A @ 30Vdc
Error Relay Output
Output Type Normally Open (NO) / Normally Closed (NC)
Contact Rate 1 A @ 30Vdc
Measured
Case Material Plastic ABS + Metal Base
IP Class IP30
Preferred Cable for Zone Connection JY(St)Y 1×2×0.8+0.8 type Fire Cable
Dimensions 26.5 × 31 × 10 cm
Weight 1.5 kg
Recommended Power Connection Cable Data Retention 3×2, 5 NYM or NYA type 10 years